contact@rmadden.com | 806-797-4251
INTEGRATED HIS FURNACE CONTROL KIT 36 IN
- Item Code: 50M56U751
- Brand: White-Rodgers
- Unit Size: 1
Description
White-Rodgers Integrated HIS Furnace Control Kit 36 in Probe Length 25 VAC 0.45 A 19 s Igniter Warm-Up Time 30 s Prepurge Retries: 2 times 275 s Lockout Surface Mount
Features
Back To Top- System diagnostic LED with fault recall
- Fused to protect low voltage system transformers
- Self-test installation routine
- Replaces white-rodgers 50M56-751 and virtually all carrier single stage HSI controls with 120V ignitors
- Controls gas valve ignitor blower inducer humidifier (both 120V and 24V) and air cleaner
- 50/60 Hz frequency
- 5 to 93% RH (non-condensing) humidity
- 1.5 A at 25 VAC 50/60 Hz 0.6 pf valve relay
- 6 A at 120 VAC 50/60 Hz ignitor relay (resistive)
- 2.2 FLA-3.5 LRA at 120 VAC inducer relay
- 14.5 FLA-25 LRA at 120 VAC circulator relay
- 0.8 sec Flame establishing time
- 2 sec maximum flame failure response time
- 25/60 sec heat delay to-fan-on
- 90/120 sec heat delay to-fan-off
- 2 sec Cool delay to-fan-on
- 5/90 sec cool delay to-fan-off
- 25 sec post purge
- -40 to 176 deg F operating temperature
Tech Specs
Back To TopAmperage Rating | 0.45 A |
---|---|
Brand | White-Rodgers |
Igniter Warm-Up Time | 19 s |
Lockout Time | 275 s |
Mounting Type | Surface |
Prepurge Time | 30 s |
Probe Length | 36 in |
Retries | 2 times |
Voltage Rating | 25 VAC |